Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No Phone volume is too low to communicate.
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Phone inside elevator does not operate. 4/28/2020
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Emergency phone does not operate 3/25/2021
A17.1-2016 : Elevators 2.31 - Relief Valves 8.6.5.14.1 No No Need to perform annual pressure relief test 4/14/2022
A17.1-1996 : Elevators 2.35 - Supply Line and Shutoff Valve 303 Yes No Replace badly rusted hydraulic supply piping and shut off valve in the pit. 3/12/2024
A17.1-2016 : Elevators 2.36 - Hydraulic Cylinders 8.6.5.14.2 Yes No Clean and paint surface of exposed cylinders to prevent deterioration from rust. 3/12/2024
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No Post the emergency evacuation of passengers procedure form inside the machine room. 11/16/2021
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No Test and log firefighter operation monthly. 11/16/2021
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No State Operating Certificate not available! 3/21/2024