Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (I) - Pits (I)1 Pit shall be cleaned, there is oil from the leaking jacks
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current operating certificate shall be displayed in the machine room
MO Minimum : Elevators (I) - Pits (I)8 Re-install sump hole cover
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Repair / replace non working pit light
MO Minimum : Elevators (I) - Pits (I)1 Repair / replace non working sump pump in pit
MO Minimum : Elevators (I) - Pits (I)1 Remove oil from sump pump hole in pit
MO Minimum : Elevators (I) - Pits (I)1 Pit shall be cleaned, there is oil from leaking jacks
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current state operating certificate shall be displayed in the machine room
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.11 - Plunger and Cylinder 8.6.5.5 Gland Packings and Seals Both jacks appear to be leaking and need to be repaired
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.11 - Plunger and Cylinder 3.18 Both jacks appear to be leaking and shall be repaired
A17.1-2016 : Elevators 5.15 - Overspeed Valve 8.6.5.16.5 x Unit has an over speed valve that shall be tested within 90 days. 3/18/2024