Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 2.35 - Supply Line and Shutoff Valve 303 Make supply line shutoff valve operational. 1/18/2019
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Display current state operating certificate. 1/18/2019
A17.1-1996 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test. 9/9/2022
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Up-to-date operating certificate is required in the machine room. 9/26/2023
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 8/24/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection Scavenger pump is not allowed in pit as amount of oil leakage cannot be determined. 8/24/2024
A17.1-1996 : Elevators 3.2 - Car top light and outlet 204.7 The car top lighting shall be operational. 8/24/2024
A17.1-1996 : Elevators 1.17 - Standby power operation 211.2 x Auxiliary power lowering operation shall work. 9/24/2024
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) x The emergency lights shall be operational. 8/6/2020
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The alarm bell shall be operational. 8/6/2020