Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts Replace missing 2x4 electrical box cover on car top. 11/20/2023
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) x Emergency lighting shall work. 11/8/2023
A17.1-1996 : Elevators 1.6 - Car emergency signal 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Two-way communication device shall work (with and without main power) and give proper location. 11/8/2023
A17.1-1996 : Elevators 2.1 - Access to machine space 101.3d Machine room door shall be self-closing and self-locking. 11/20/2023
A17.1-1996 : Elevators 2.1 - Access to machine space 101.3d The machine room door shall be self-closing and self-locking and shall be operable from the interior space without the use of a key. The door is not self-closing. 11/20/2023
A17.1-1996 : Elevators 2.4 - Machine space 1001.2(b)(4) The elevator machine and control equipment shall be located in a separate room or separated space designed as an elevator machine room or space and shall be accessible only to authorized personnel. 10/7/2021
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 10/7/2021
A17.1-1996 : Elevators 2.5 - Housekeeping 1206.2b (Clean Machine Room) Non-elevator related items shall not be stored in machine room (heaters, buckets, water shutoff key, etc). 11/20/2023
A17.1-1996 : Elevators 2.5 - Housekeeping 1206.2c (Clean Car Tops) Clean top of car. 11/20/2023
A17.1-1996 : Elevators 3.10 - Hoistway construction 1001.2(c)(16) Patch holes in the hoistway walls. 10/7/2021
A17.1-1996 : Elevators 3.12 - Pipes, wiring, and ducts 1001.2(c)(18) All electrical wiring in the hoistway shall be enclosed in metal conduit, flexible conduit, or metal raceway, or be in compliance with NFPA 70. 10/7/2021
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits Pit light shall work. 12/3/2018
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1 The pit shall be kept clean. Remove excess debris. 11/20/2023
A17.1-1996 : Elevators 5.11 Plunger and Cylinder 1206.5b(4) The cylinder packing is leaky and shall be monitored. 10/1/2019
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be obtained and displayed in the elevator machine room. 10/7/2021
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 11/20/2023
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 11/20/2023