Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting Ceiling panels in car are egg crate type, providing no protection for passengers, Replace panels with solid type or install plastic tubes & end caps over bulbs 11/23/2023
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) Machine room light shall work, bulb appears good 11/23/2023
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone shall be made operable. Re-inspection required 9/7/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.1 General Maintenance Requirements Documentation A written maintenance control program shall be kept on site 11/23/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing OSV is due for a full load test & tripping speed checked. Re-inspection required 11/1/2023