Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 2.5 - Housekeeping 1001.2(b)(5) Machine space shall not be used for storage. 11/4/2019
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1206.1h The fire extinguisher in the machine room is expired.
A17.1-1996 : Elevators 1.6 - Car emergency signal 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The in car emergency telephone shall be operational. 4/21/2023
A17.1-1996 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing (Re-Inspection) x Elevator is equipped with an unsealed overspeed valve. A category 5 test is required. The valve shall be tagged and sealed after a successful category 5 test. 4/21/2023
A17.1-1996 : Elevators 2.5 - Housekeeping 1206.2b (Clean Machine Room) Non-elevator related items shall not be stored in the machine room. (Electric mower, lawncare equipment, etc.)
A17.1-2016 : Elevators 5.15 - Overspeed Valve 8.6.5.16.5 OSV in pit is not sealed, provide testing per MFG, Leave written procedures on site. Tag and seal upon completion 12/1/2022
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(a) Provide MCP 12/1/2022
A17.1-2016 : Elevators 1.17 - Standby power operation 8.11.3.1.1(q) x Existing auxiliary power unit not working, repair as needed 11/21/2022