                        A17.1-1996 : Elevators
                     | 
                    
                        2.5 - Housekeeping
                     | 
                    
                        1001.2(b)(5)
                     | 
                    
                     | 
                    
                     | 
                    
                        Machine space shall not be used for storage.
                     | 
                    
                        11/4/2019
                     | 
                
                
                    | 
                        A17.1-1996 : Elevators
                     | 
                    
                        2.7 - Fire Extinguisher
                     | 
                    
                        1206.1h
                     | 
                    
                     | 
                    
                     | 
                    
                        The fire extinguisher in the machine room is expired.
                     | 
                    
                        
                     | 
                
                
                    | 
                        A17.1-1996 : Elevators
                     | 
                    
                        2.5 - Housekeeping
                     | 
                    
                        1206.2b (Clean Machine Room)
                     | 
                    
                     | 
                    
                     | 
                    
                        Non-elevator related items shall not be stored in the machine room. (Electric mower, lawncare equipment, etc.)
                     | 
                    
                        
                     | 
                
                
                    | 
                        A17.1-1996 : Elevators
                     | 
                    
                        1.6 - Car emergency signal
                     | 
                    
                        211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
                     | 
                    
                            x
                     | 
                    
                     | 
                    
                        Elevator phone failed Cat 1 Emergency communications test, phone is not working. Re-inspection required
                     | 
                    
                        
                     | 
                
                
                    | 
                        A17.1-1996 : Elevators
                     | 
                    
                        1.6 - Car emergency signal
                     | 
                    
                        306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
                     | 
                    
                            x
                     | 
                    
                     | 
                    
                        The in car emergency telephone shall be operational.
                     | 
                    
                        4/21/2023
                     | 
                
                
                    | 
                        A17.1-2016 : Elevators
                     | 
                    
                        1.17 - Standby power operation
                     | 
                    
                        8.11.3.1.1(q)
                     | 
                    
                            x
                     | 
                    
                     | 
                    
                        Existing auxiliary power unit not working, repair as needed
                     | 
                    
                        11/21/2022
                     | 
                
                
                    | 
                        A17.1-2016 : Elevators
                     | 
                    
                        2.40 - Maintenance Records
                     | 
                    
                        8.6.1.2.1(a)
                     | 
                    
                     | 
                    
                     | 
                    
                        Provide MCP
                     | 
                    
                        12/1/2022
                     | 
                
                
                    | 
                        MO Minimum : Elevators
                     | 
                    
                        (G) - Maintenance, Repair and Replacements
                     | 
                    
                        8.6.1.6.5 Fire Extinguishers
                     | 
                    
                     | 
                    
                     | 
                    
                        Fire extinguisher is expired, have serviced or replaced
                     | 
                    
                        
                     | 
                
                
                    | 
                        A17.1-2016 : Elevators
                     | 
                    
                        5.15 - Overspeed Valve
                     | 
                    
                        8.6.5.16.5
                     | 
                    
                     | 
                    
                     | 
                    
                        OSV in pit is not sealed, provide testing per MFG, Leave written procedures on site. Tag and seal upon completion
                     | 
                    
                        12/1/2022
                     | 
                
                
                    | 
                        A17.1-1996 : Elevators
                     | 
                    
                        11 CSR 40-5.090 Inspection and Testing
                     | 
                    
                        8.6.5.16.5 Over Speed Valve Testing (Re-Inspection)
                     | 
                    
                            x
                     | 
                    
                     | 
                    
                        Elevator is equipped with an unsealed overspeed valve. A category 5 test is required. The valve shall be tagged and sealed after a successful category 5 test.
                     | 
                    
                        4/21/2023
                     |