Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion n/a The hoistway door at the top landing is missing the access plunger. Replace the missing plunger to allow maintenance and emergency personnel to access the hoistway. 1/15/2019
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The elevator ADA telephone inside the elevator is not working properly. Check and repair the programming of this phone for proper operation and passenger safety. 4/30/2019
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) x The emergency car lighting is not operational, likely indicating that the back-up power device (battery) has failed. The fixture shall be repaired to operate. Reinspection required. 2/5/2020
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1002.2f x The fireman's emergency service phase I and II operations was tested and the following deficiency was noted: The fireman’s service phase I key switch bezel is missing and shall be replaced to activate/operate as required. 3/10/2022