A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.6.4.19.6
|
Yes
|
No
|
During the phase I fire service test, the audible signaling device inside the elevator cab failed to sound, needs repaired. Rr-inspection required
|
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.19 - Guide rails fastening and equipment
|
8.6.4.3
|
No
|
No
|
Car guide shoes need to be replaced.
|
2/20/2020
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
Yes
|
No
|
Emergency phone needs to have message, location.
|
5/16/2019
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
Yes
|
No
|
Alarm bell shall work.
|
5/16/2019
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
No
|
No
|
Maintenance control program shall have written procedures for inspection and testing located on-site.
|
9/25/2020
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.2.1 Repair Parts
|
No
|
No
|
Exhaust fan in the machine room does not work, needs repaired to provide adequate temperature control
|
|