A17.1-1996 : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing (Re-Inspection)
|
x
|
|
OSV is overdue for testing as noted in last inspection. Perform required testing, seal & tag within 90 days. Re-inspection required
|
8/3/2022
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A copy of the current state operating certificate shall be displayed in the machine room.
|
|
A17.1-1996 : Elevators
|
2.3 - Lighting and receptacles
|
101.5a Lighting
|
|
|
Repair machine room lighting so that there is 10 foot candles of light at the floor.
|
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
102
|
x
|
|
Repair pit light.
|
6/11/2019
|
A17.1-1996 : Elevators
|
2.3 - Lighting and receptacles
|
101.5c Receptacles
|
|
|
Repair machine room lights.
|
8/30/2018
|
A17.1-2016 : Elevators
|
5.15.2 Unsealed Overspeed Valve
|
8.6.5.16.5 (Re-Inspect)
|
x
|
|
OSV is not sealed. Noted on last inspection 2021 requirement to test.
|
6/28/2022
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone in car does not work. Re-inspection required
|
|