Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (O) - Existing Hydraulic Elevators (O)2(D) Emergency light not working. Reinspect. 1.6 8/29/2018
MO Minimum : Elevators (H) - Machine Rooms (H)1 Fire extinguisher outdated. 2.7 8/29/2018
MO Minimum : Elevators (I) - Pits (I)1 Pit shall be kept clean and dry. 10/21/2019
MO Minimum : Elevators (I) - Pits (I)1 Sump pump needs to be repaired or replaced so that it operates automatically. 10/21/2019
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Lighting and electrical plugs in pit shall be replaced. If installed below 4 ft it needs to be NEMA 4 waterproof. 10/21/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Buffer stands and pit channels are rusted. Should be rust proof to prevent further damage. 10/21/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Hydraulic lines should be checked and rust proofed to prevent further damage. 10/21/2019
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Emergency phone does not work. REINSPECT REQUIRED 8/12/2021
MO Minimum : Elevators (I) - Pits (I)1 Sump pump in pit is not pumping. There is standing water in the pit. All pits shall be kept dry, clean, and free of equipment or material not relating to the operation of the elevator.
MO Minimum : Elevators (I) - Pits (I)1 There is standing water in the pit. The sump pump does not turn on automatically. Pits shall be kept clean, dry, and clear of debris.
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) The pit light does not illuminate
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) x x Emergency Light does not work when normal power is removed. The alarm bell does work on backup power 9/3/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x Emergency Light and Bell do not work when normal power is removed 8/9/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency phone not working. Only 14 volts on phone line. 10/15/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Repair emergency light, alarm bell and phone. 10/15/2020