MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)7
|
|
|
Door force exceeds 30#, adjust as needed.
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Provide existing phone in car to work. Has 52v. Has no key pad, does not work correctly.
|
9/7/2023
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)7
|
x
|
|
Car door force exceeds 30#, adjust as needed
|
9/7/2023
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Phone in car has power, but doesn't work. Repair or replace. Re-inspection required
|
9/7/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4.1(a) On-Site Maintenance Records (MCP Records)
|
x
|
|
A written copy of the MCP shall be kept in the machine room for each unit
|
9/7/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.2.1 General Maintenance Requirements Documentation
|
|
|
Provide MCP.
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)4
|
|
|
Machine room shall not be used for storage for items that are not related to the maintenance or operation of the elevator
|
3/14/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Repair emergency light and alarm bell.
|
10/15/2020
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Car failed 15 minute stand test, tech determined it to be leaking back through the valve. Repair as needed, reinspect.
|
9/7/2023
|