Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)7 Door force exceeds 30#, adjust as needed.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.1 General Maintenance Requirements Documentation Provide MCP.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Repair emergency light and alarm bell. 10/15/2020
MO Minimum : Elevators (H) - Machine Rooms (H)4 Machine room shall not be used for storage for items that are not related to the maintenance or operation of the elevator 3/14/2022
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Provide existing phone in car to work. Has 52v. Has no key pad, does not work correctly. 9/7/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Car failed 15 minute stand test, tech determined it to be leaking back through the valve. Repair as needed, reinspect. 9/7/2023
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)7 x Car door force exceeds 30#, adjust as needed 9/7/2023
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Phone in car has power, but doesn't work. Repair or replace. Re-inspection required 9/7/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) x A written copy of the MCP shall be kept in the machine room for each unit 9/7/2023