Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods The emergency rescue battery in the controller has not been changed since 2019. The manufacture’s recommendation for replacement is 3 years. Replacement of the battery before the elevator shuts down due to battery being depleted is required. 3/26/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2 x Perform the required Cat 1 testing of the emergency generator 2/10/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.5 - Car lighting and receptacles 8.6.4.15 Emergency Lighting x The emergency light fixture inside the elevator is not operational and shall be repaired. Reinspection required. 1/24/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.5 - Car lighting and receptacles 8.6.4.15 Emergency Lighting x Provide existing emergency lights to work 2/15/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.5 - Car lighting and receptacles 8.6.4.15 Emergency Lighting x The emergency car lighting is not operational, likely indicating that the back-up power device (battery) has failed. The fixture shall be repaired to operate. Reinspection required. 4/10/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x x The testing has not been completed on the elevator at this time, the elevator was placed out of service due to governor failure. The weight test shall be performed, safeties set, and buffers compressed before the inspection is completed. 1/24/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.13 - Governor,overspeed switch and seal 2.18 x x Upon performing the required five year full load, the elevator safety governor was found to be worn to a degree that the pull-through force was overly excessive and could potentially permanently damage the elevator safeties if testing proceeded. The elevator has been removed from service. Repair or replacement of the governor is required and a reinspection shall be performed before the elevator can be returned to service. 1/24/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.3 - Lighting and receptacles 2.7.5.1 Lighting There are a number of machine room lighting fixtures that are not operational on the day of inspection. Repair lighting for proper illumination for maintenance and emergency personnel. 3/26/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.6 - Ventilation 2.7.5.2 The HVAC unit in the machine room shall be repaired to provide proper operation temperature for the elevator controller. 7/27/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.6 - Ventilation 2.7.5.2 The HVAC unit in the machine room shall be repaired to provide proper operation temperature for the elevator controller. 7/27/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.6 - Ventilation 2.8.4 The HVAC unit in the machine room shall be repaired to provide proper operation temperature for the elevator controller. 7/27/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.2 - Hoistway doors 8.6.4.13 The hoistway door retaining gib on the hoistway door is missing on the 7th floor. Reinstall missing gib to retain the hoistway door in the sill properly. 7/27/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current State Elevator Certificate.