Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2 x Perform the required Cat 1 testing of the emergency generator 2/10/2025
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current State Elevator Certificate. 6/15/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts Repair blower on hvac unit to provide proper temperature control for the machine room 7/27/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods The emergency rescue battery in the controller has not been changed since 2019. The manufacture’s recommendation for replacement is 3 years. Replacement of the battery before the elevator shuts down due to battery being depleted is required. 3/26/2024
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1002.2f x The fireman's emergency service phase I and II operations was tested and the following deficiency was noted: The “call cancel” button is not labeled inside the car and shall be labeled correctly. 4/10/2023
A17.1-1996 : Elevators 2.6 - Ventilation 102.4 The HVAC unit in the machine room shall be repaired to provide proper operation temperature for the elevator controller. 7/27/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.6 - Ventilation 2.7.5.2 The HVAC unit in the machine room shall be repaired to provide proper operation temperature for the elevator controller. 8/9/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.6 - Ventilation 2.7.5.2 The HVAC unit in the machine room shall be repaired to provide proper operation temperature for the elevator controller. 7/27/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x The testing has not been completed on this elevator, elevator G4 was removed from service and complete inspection of this elevator could not be performed. Machine room and fireman’s service were only completed on this unit at this time, reinspection is required. 2/14/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x The testing has not been completed on this elevator, the elevator was removed from service and complete inspection of this elevator could not be performed. The governor failed inspection and the safeties could not be set. A reinspection is required. 4/10/2023
A17.1-1996 : Elevators 2.3 - Lighting and receptacles 101.5a Lighting There are a number of machine room lighting fixtures that are not operational on the day of inspection. Repair lighting for proper illumination for maintenance and emergency personnel. 3/26/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.13 - Governor,overspeed switch and seal 2.18 x x Upon performing the required five year full load, the elevator safety governor was found to be worn to a degree that the pull-through force was overly excessive and could potentially permanently damage the elevator safeties if testing proceeded. The elevator has been removed from service. Repair or replacement of the governor is required. This shall require an alteration permit, alteration inspection and a reinspection performed before the elevator will have a certificate of compliance issued. 4/10/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.13 - Governor,overspeed switch and seal 2.18 x Upon pre-inspecting this governor for the required five year full load, the elevator safety governor was found to be worn to a degree that per the manufacturer specifications it shall be “replaced within 6 months”. Repair or replacement of the governor is required. This shall require an alteration permit, alteration inspection and a reinspection performed before the elevator will have a certificate of compliance issued. 2/14/2023