MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)8 Car Lighting
|
|
|
The cab ceiling is of the open type, which does not provide protection from the light bulbs should they shatter. The lights shall be guarded by plastic sleeve or some other means to properly protect passengers.
|
7/27/2023
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)8 Car Lighting
|
|
|
A number of lighting fixtures in the elevator cab have been damaged and shall be repaired to at least provide not less than five (5) foot-candles of lighting throughout the cab.
|
7/27/2023
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)8 Car Lighting
|
|
|
The cab ceiling is of the open type, which does not provide protection from the light bulbs should they shatter. The lights shall be guarded by plastic sleeve or some other means to properly protect passengers.
|
8/9/2023
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)8 Car Lighting
|
|
|
A number of lighting fixtures in the elevator cab have been damaged and shall be repaired to at least provide not less than five (5) foot-candles of lighting throughout the cab.
|
8/9/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13 - Door systems
|
|
|
Hoistway door gibs are missing on floors 6 and 22. A hoistway door fire tab is missing on the 2nd floor. Reinstall gibs and fire tab at the locations noted.
|
8/9/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13 - Door systems
|
|
|
Replace missing door Gibs at floors 6 and 11
|
3/26/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13 - Door systems
|
|
|
Replace missing fire tab at 2nd floor
|
3/26/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13 - Door systems
|
|
|
Replace cover on thw 2nd fllor door lock
|
3/26/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13 - Door systems
|
|
|
Hoistway door gibs are missing on floors 6 and 22. A hoistway door fire tab is missing on the 2nd floor. Reinstall gibs and fire tab at the locations noted.
|
7/27/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13 - Door systems
|
|
|
The hoistway door interlock cover is missing on the 2nd floor, reinstall cover to prevent accidental contact with the electrical interlocks.
|
8/9/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13 - Door systems
|
|
|
Hoistway door gibs are missing on floors 6 and 22. A hoistway door fire tab is missing on the 2nd floor. Reinstall gibs and fire tab at the locations noted.
|
8/23/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13 - Door systems
|
|
|
The hoistway door interlock cover is missing on the 2nd floor, reinstall cover to prevent accidental contact with the electrical interlocks.
|
8/23/2023
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
1002.2f
|
x
|
|
The fireman’s service phase I key switch has degraded and shall be replaced. The key switch will not allow the phase I key to be removed without great difficulty.
|
4/10/2023
|
A17.1-1996 : Elevators
|
2.3 - Lighting and receptacles
|
101.5c Receptacles
|
|
|
Replace bulbs that are out in machine room.
|
5/26/2020
|
A17.1-1996 : Elevators
|
2.7 - Fire Extinguisher
|
1206.1h
|
|
|
Update fire extinguisher in machine room.
|
5/26/2020
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
1206.2a (Pits and Hoistways)
|
|
|
Clean pit.
|
3/26/2024
|
A17.1-1996 : Elevators
|
1.7 - Car door or gate
|
204.5
|
|
|
Replace missing 24th floor fire tab
|
|
A17.1-1996 : Elevators
|
1.5 - Car lighting and receptacles
|
204.7
|
|
|
All lights in the elevator cab shall be protected or be above the drop ceiling.
|
5/26/2020
|
A17.1-1996 : Elevators
|
1.5 - Car lighting and receptacles
|
204.7
|
|
|
Replace ceiling panels or guard bulbs inside car.
|
5/26/2020
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
211.1(a)(3) Battery Backup Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Repair emergency alarm, not functioning on battery backup
|
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
211.7 Firefighter' Service Operating Procedures
|
|
|
The fireman's emergency service phase I and II operations was tested and the following deficiency was noted: The “call cancel” button is not labeled inside the car and shall be labeled correctly.
|
8/9/2023
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
211.8 Switch Keys
|
x
|
|
The fireman’s service phase I key switch has degraded and shall be replaced. The key switch will not allow the phase I key to be removed without great difficulty
|
2/13/2024
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Display updated certificate in machine room.
|
5/26/2020
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection)
|
x
|
|
The fireman’s service phase I key switch has degraded and shall be replaced. The key switch will not allow the phase I key to be removed without great difficulty
|
4/10/2023
|
A17.1-1996 : Elevators
|
2.42 - Earthquake Inspection and Tests (Seismic Risk Zone 2 or Greater)
|
8.4.10.1.2 - Protection not functioning
|
x
|
|
The seismic device on the counterweight did not initiate when activated. Repair device to operate when activated
|
4/10/2023
|
A17.1-1996 : Elevators
|
2.42 - Earthquake Inspection and Tests (Seismic Risk Zone 2 or Greater)
|
8.4.10.1.2 - Protection not functioning
|
x
|
|
The seismic device on the counterweight did not initiate when activated. Repair device to operate when activated.
|
4/10/2023
|
A17.1-1996 : Elevators
|
2.42 - Earthquake Inspection and Tests (Seismic Risk Zone 2 or Greater)
|
8.4.10.1.2 - Protection not functioning
|
x
|
|
Seismic, ring and string, failed to trigger on test. Repair.
|
11/1/2022
|
A17.1-2016 : Elevators
|
2.42 - Earthquake Inspection and Tests (Seismic Risk Zone 2 or Greater)
|
8.6.4.19.17 Earthquake Operation
|
|
|
The seismic device on the counterweight did not initiate when activated. Repair device to operate when activated.
|
2/13/2024
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
x
|
|
Perform the required annual testing of the emergency power generator
|
|
conversion
|
conversion
|
n/a
|
|
|
Replace hoist cables (Rouge)
|
10/1/2018
|
conversion
|
conversion
|
n/a
|
|
|
Replace ceiling or install guards on cab flourscents.
|
5/26/2020
|