MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
All pits shall be kept dry, clean, and free of equipment or material not relating to the operation of the elevator. (Standing water in pit)
|
|
MO Minimum : Elevators
|
(F) - Electrical Switches
|
(F)1
|
x
|
|
Car top inspection station, up button needs to work.
|
10/11/2019
|
A17.1-1996 : Elevators
|
3.3 - Top-of-car operating device
|
210.1d
|
|
|
Car top inspection up button needs to be operational
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency Phone in car fails to establish two-way communication. It needs to be programmed
|
|
A17.1-1996 : Elevators
|
3.3 - Top-of-car operating device
|
1001.2(c)(3)
|
|
|
Inspection station on top of car not working. Will not run up
|
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.1(a)
|
|
|
MCP violation
|
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.2(a) On-Site Documentation (Up-to-Date Wiring Diagrams)
|
|
|
No wiring diagrams
|
|
A17.1-2016 : Elevators
|
5.15 - Overspeed Valve
|
8.6.5.16.5
|
|
|
Overspeed valves, where provided, shall be inspected and tested to verify that they will stop the car, traveling down with rated load. Missing seal on valve
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Test incomplete. Perform the governor and pressure test to complete the annual
|
10/31/2022
|