Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (I) - Pits (I)1 All pits shall be kept dry, clean, and free of equipment or material not relating to the operation of the elevator. (Standing water in pit)
MO Minimum : Elevators (F) - Electrical Switches (F)1 x Car top inspection station, up button needs to work. 10/11/2019
A17.1-1996 : Elevators 3.3 - Top-of-car operating device 210.1d Car top inspection up button needs to be operational
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency Phone in car fails to establish two-way communication. It needs to be programmed
A17.1-1996 : Elevators 3.3 - Top-of-car operating device 1001.2(c)(3) Inspection station on top of car not working. Will not run up
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(a) MCP violation
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.2(a) On-Site Documentation (Up-to-Date Wiring Diagrams) No wiring diagrams
A17.1-2016 : Elevators 5.15 - Overspeed Valve 8.6.5.16.5 Overspeed valves, where provided, shall be inspected and tested to verify that they will stop the car, traveling down with rated load. Missing seal on valve
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Test incomplete. Perform the governor and pressure test to complete the annual 10/31/2022