Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.1 General Maintenance Requirements Documentation Yes No Isolation pads under suspension cable shackle springs in the machine room are either deteriorated or missing. Replace isolation pads. Re-inspection required 4/24/2026
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Elevator cab phone does not work, needs repaired. Re-inspection required 4/24/2026
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Elevator cab phone does not work, needs repaired. Re-inspection required
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Elevator cab phone does not work, needs repaired. Re-inspection required 4/16/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Test incomplete. Inspected hoistway, elevator pit, tested phase I and II fire service, tested cab phone, emergency lights and alarm bell 9/19/2023
A17.1-1996 : Elevators 2.29 - Car and counterweight safeties Table 205.3 Yes Yes Elevator car safeties are stopping the car too fast with the rated load. Slide shall be no less than 13 inches. Current slide is 8 inches. Red tag 9/20/2023
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No Provide on-site maintenance control program. 6/16/2021
A17.1-2016 : Elevators 2.5 - Housekeeping 8.6.4.9 Cleaning of Top of Cars No No Clean dirt & debris from elevator car top 4/24/2026
A17.1-2016 : Elevators 3.23 - Suspension Means 8.6.3.2 (Re-Inspection) Yes Yes Elevator suspension cables are severely rouged and many layers have gaps between adjacent layers showing signs of internal breakage.. Red-tagged, removed from service. Re-inspection required 4/24/2026
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post current operating certificate in machine room. 6/16/2021