A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
Yes
|
No
|
Elevator cab phone does not work, needs repaired. Re-inspection required
|
|
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
No
|
No
|
Post current operating certificate in machine room.
|
6/16/2021
|
|
A17.1-1996 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
No
|
No
|
Provide on-site maintenance control program.
|
6/16/2021
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
Yes
|
No
|
Test incomplete. Inspected hoistway, elevator pit, tested phase I and II fire service, tested cab phone, emergency lights and alarm bell
|
9/19/2023
|
|
A17.1-1996 : Elevators
|
2.29 - Car and counterweight safeties
|
Table 205.3
|
Yes
|
Yes
|
Elevator car safeties are stopping the car too fast with the rated load. Slide shall be no less than 13 inches. Current slide is 8 inches. Red tag
|
9/20/2023
|
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
Yes
|
No
|
Elevator cab phone does not work, needs repaired. Re-inspection required
|
4/16/2025
|
|
A17.1-2016 : Elevators
|
2.5 - Housekeeping
|
8.6.4.9 Cleaning of Top of Cars
|
No
|
No
|
Clean dirt & debris from elevator car top
|
4/24/2026
|
|
A17.1-2016 : Elevators
|
3.23 - Suspension Means
|
8.6.3.2 (Re-Inspection)
|
Yes
|
Yes
|
Elevator suspension cables are severely rouged and many layers have gaps between adjacent layers showing signs of internal breakage.. Red-tagged, removed from service. Re-inspection required
|
4/24/2026
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.2.1 General Maintenance Requirements Documentation
|
Yes
|
No
|
Isolation pads under suspension cable shackle springs in the machine room are either deteriorated or missing. Replace isolation pads. Re-inspection required
|
4/24/2026
|
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
Yes
|
No
|
Elevator cab phone does not work, needs repaired. Re-inspection required
|
4/24/2026
|