Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current operating certificate in machine room. 6/16/2021
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 Provide on-site maintenance control program. 6/16/2021
A17.1-1996 : Elevators 2.29 - Car and counterweight safeties Table 205.3 x x Elevator car safeties are stopping the car too fast with the rated load. Slide shall be no less than 13 inches. Current slide is 8 inches. Red tag 9/20/2023
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Elevator cab phone does not work, needs repaired. Re-inspection required 4/16/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Test incomplete. Inspected hoistway, elevator pit, tested phase I and II fire service, tested cab phone, emergency lights and alarm bell 9/19/2023