MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Test incomplete. Inspected hoistway, elevator pit, tested phase I and II fire service, tested cab phone, emergency lights and alarm bell
|
9/19/2023
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current operating certificate in machine room.
|
6/16/2021
|
A17.1-1996 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
Provide on-site maintenance control program.
|
6/16/2021
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Elevator cab phone does not work, needs repaired. Re-inspection required
|
4/16/2025
|
A17.1-1996 : Elevators
|
2.29 - Car and counterweight safeties
|
Table 205.3
|
x
|
x
|
Elevator car safeties are stopping the car too fast with the rated load. Slide shall be no less than 13 inches. Current slide is 8 inches. Red tag
|
9/20/2023
|