Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1 Hydraulic pipe in pit is rusted. Take corrective action as needed.
A17.1-1996 : Elevators 2.1 - Access to machine space 1001.2(b)(1) The machine room door shall be self-closing and self-locking. 10/25/2019
A17.1-1996 : Elevators 2.3 - Lighting and receptacles 1001.2(b)(3) Inspection code The machine room lighting shall work. 10/25/2019
A17.1-1996 : Elevators 2.5 - Housekeeping 1001.2(b)(5) The machine room shall be cleaned of dirt and debris. 10/25/2019
A17.1-1996 : Elevators 3.23 - Suspension rope 1001.2(c)(29) x A rope data tag is required on the hoist ropes. 10/25/2019
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits The pit light shall work. 10/25/2019
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1001.2(d)(12) - A fire service testing log shall be kept on-site. 10/25/2019
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 A maintenance log shall be kept on-site. 10/25/2019
A17.1-1996 : Elevators 3.23 - Suspension rope 1001.2(c)(29) x The hoist ropes are rouging and have crown breaks and require replacement. 10/25/2019
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The in car emergency telephone shall be operational. 10/8/2020
A17.1-1996 : Elevators 2.34 - Flexible Hydraulic Hose and Fitting Assemblies 1004.2(b)(17) The high pressure hose is expired. If the unit is equipped with a rupture valve the hose does not need replacing, if no rupture valve is present the high pressure hose shall be replaced. 2/22/2021
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The in car emergency telephone shall be operational. 2/23/2021
A17.1-1996 : Elevators 1.2 - Stop switches 1001.2(a)(2) The in car stop switch does not stop the elevator. Repair or replace the switch for proper operation. 2/24/2021
A17.1-2016 : Elevators 5.15.2 Unsealed Overspeed Valve 8.6.5.16.5 (Re-Inspect) x OSV is not sealed. Perform test, tag, and seal upon completion. 7/27/2021
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 7/11/2023
A17.1-1996 : Elevators 3.2 - Car top light and outlet 204.7 Top of hoistway light shall be operational. 7/11/2023