A17.1-1996 : Elevators
|
2.1 - Access to machine space
|
1001.2(b)(1)
|
|
|
The machine room door shall be self-closing and self-locking.
|
10/25/2019
|
A17.1-1996 : Elevators
|
2.3 - Lighting and receptacles
|
1001.2(b)(3) Inspection code
|
|
|
The machine room lighting shall work.
|
10/25/2019
|
A17.1-1996 : Elevators
|
2.5 - Housekeeping
|
1001.2(b)(5)
|
|
|
The machine room shall be cleaned of dirt and debris.
|
10/25/2019
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
106.1e Illumination of Pits
|
|
|
The pit light shall work.
|
10/25/2019
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
1001.2(d)(12) -
|
|
|
A fire service testing log shall be kept on-site.
|
10/25/2019
|
A17.1-1996 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
A maintenance log shall be kept on-site.
|
10/25/2019
|
A17.1-1996 : Elevators
|
2.34 - Flexible Hydraulic Hose and Fitting Assemblies
|
1004.2(b)(17)
|
|
|
The high pressure hose is expired. If the unit is equipped with a rupture valve the hose does not need replacing, if no rupture valve is present the high pressure hose shall be replaced.
|
2/22/2021
|
A17.1-1996 : Elevators
|
1.2 - Stop switches
|
1001.2(a)(2)
|
|
|
The in car stop switch does not stop the elevator. Repair or replace the switch for proper operation.
|
2/24/2021
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
7/11/2023
|
A17.1-1996 : Elevators
|
3.2 - Car top light and outlet
|
204.7
|
|
|
Top of hoistway light shall be operational.
|
7/11/2023
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
106.1
|
|
|
Hydraulic pipe in pit is rusted. Take corrective action as needed.
|
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The in car emergency telephone shall be operational.
|
2/23/2021
|
A17.1-2016 : Elevators
|
5.15.2 Unsealed Overspeed Valve
|
8.6.5.16.5 (Re-Inspect)
|
x
|
|
OSV is not sealed. Perform test, tag, and seal upon completion.
|
7/27/2021
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The in car emergency telephone shall be operational.
|
10/8/2020
|
A17.1-1996 : Elevators
|
3.23 - Suspension rope
|
1001.2(c)(29)
|
x
|
|
The hoist ropes are rouging and have crown breaks and require replacement.
|
10/25/2019
|
A17.1-1996 : Elevators
|
3.23 - Suspension rope
|
1001.2(c)(29)
|
x
|
|
A rope data tag is required on the hoist ropes.
|
10/25/2019
|