Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 Provide on-site maintenance records. 9/1/2020
A17.1-1996 : Elevators 1.17 - Standby power operation 1002.2g (Standby Power Operation) x Emergency battery lowering device is not working, needs repaired. Re-inspection required 5/21/2024
A17.1-2016 : Elevators 5.15.2 Unsealed Overspeed Valve 8.6.5.16.5 (Re-Inspect) x OSV is not sealed and must have a category 5 weight test performed within 90 days or less 9/28/2021
A17.1-2016 : Elevators 5.15 - Overspeed Valve 8.6.5.16.5 OSV test only, Down car speed is 100 FPM, OSV tripped at 117 FRM 11/15/2021
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Pit light is not working, needs repaired 5/21/2024