MO Minimum : Elevators
|
(F) - Electrical Switches
|
(F)1
|
x
|
|
There shall be a switch in the disconnect that will not activate the emergency lowering device when the disconnect is turned off. Re-inspection required
|
3/31/2025
|
MO Minimum : Elevators
|
(F) - Electrical Switches
|
(F)9
|
|
|
There shall be a switch in the disconnect that will not activate the emergency lowering device when the disconnect is turned off
|
|
A17.1-1996 : Elevators
|
1.17 - Standby power operation
|
1001.2(a)(17)
|
x
|
|
Battery backup lowering unit not working correctly, repair/replace as needed.
|
5/2/2023
|
A17.1-1996 : Elevators
|
2.36 - Hydraulic Cylinders
|
1004.2(b)(19)
|
|
|
Remove scavenger line from tank.
|
|
A17.1-1996 : Elevators
|
2.36 - Hydraulic Cylinders
|
1004.2(b)(19)
|
|
|
Remove scavenger pump unit from pit.
|
|
A17.1-1996 : Elevators
|
2.36 - Hydraulic Cylinders
|
1004.2(b)(19)
|
x
|
|
Remove scavenger line from the tank.
|
|
A17.1-1996 : Elevators
|
2.36 - Hydraulic Cylinders
|
1004.2(b)(19)
|
x
|
|
Remove scavenger unit from the pit.
|
|
A17.1-1996 : Elevators
|
5.11 Plunger and Cylinder
|
1206.5b(5) Oil Leakage Collection
|
|
|
Cylinder head packing is worn and leaking, repair as needed.
|
|
A17.1-1996 : Elevators
|
1.17 - Standby power operation
|
211.2
|
x
|
|
Provide existing battery backup lowering unit to work properly.
|
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
3.26.10
|
x
|
|
Emergency lowering device shall be made operational. Re-inspection required
|
6/17/2024
|
A17.1-1996 : Elevators
|
2.36 - Hydraulic Cylinders
|
302.3
|
|
|
Provide pit bucket.
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current State Elevator Certificate.
|
|
A17.1-1996 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
Provide MCP.
|
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
x
|
|
Emergency lowering device is not working. Re-inspection required
|
3/31/2025
|
A17.1-2016 : Elevators
|
5.15.2 Unsealed Overspeed Valve
|
8.6.5.16.5 (Re-Inspect)
|
x
|
|
Unsealed.
|
5/2/2023
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing
|
|
|
OSV is not sealed or tagged. Shall be tested within 30 days.
|
|
A17.1-1996 : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing
|
|
|
OSV is not sealed. Perform OSV test on or before next annual inspection.
|
6/4/2021
|