MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)4
|
|
|
Items not related to the operation of the elevator not to be stored in the machine room
|
7/27/2022
|
A17.1-1996 : Elevators
|
1.18 - Restricted opening of car or hoistway doors
|
1001.2(a)(18)
|
x
|
|
Repair front amd rear door restrictors
|
1/21/2020
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
When 110ac is turned off to car, emergency light and alarm don't work
|
1/21/2020
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.1(a)
|
|
|
A written Maintenance Control Program shall be in place to maintain the equipment in compliance with the requirements of Section 8.6
|
7/27/2022
|
A17.1-1996 : Elevators
|
2.5 - Housekeeping
|
1001.2(b)(5)
|
|
|
Machine room not to be used for storage
|
6/11/2020
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
106.1e Illumination of Pits
|
|
|
Remove oil from pit
|
6/11/2020
|
A17.1-2016 : Elevators
|
5.15 - Overspeed Valve
|
8.6.5.16.5
|
|
|
Overspeed valves, where provided, shall be inspected and tested to verify that they will stop the car, traveling down with rated load. If the seal has been altered or broken, the overspeed valve shall be resealed after successful test
|
7/27/2022
|