MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
|
Per MEMORANDUM 005 A17.1.2016 Section 8.6.5.16.5 Overspeed Valve must be tested/Set and Tagged. Installed in 1998 not tagged.
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
Machine room door needs to be self closing
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
|
|
The single bulb work Light fixture needs replaced with a Dual lamp fixture with lamp guard and have a minimum of 10FC Luxi lite.
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)8
|
|
|
Pit Sump hole shall have a non-combustible cover.
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)8
|
|
|
Sump pump hole has homemade wooden frame sitting on the top of pit floor over hole.
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)8
|
|
|
Pit sump hole needs non combustible cover
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection)
|
x
|
|
Electric Edge on car door is not overridden on Phase I recall.
|
7/31/2024
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection)
|
x
|
|
Elevator in car stop switch shall be overridden when Elevator is in Phase 1 after doors close and in return mode to the main egress landing.
|
7/31/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4.1(a) On-Site Maintenance Records (MCP Records)
|
|
|
MCP needed
|
|
A17.1-2016 : Elevators
|
5.15 - Overspeed Valve
|
8.6.5.16.5
|
x
|
|
Section 8.6.5.16.5 Overspeed Valves where provided shall be tested & verified. Overspeed valve does not have a test tag must test with Rated Load.
|
|