Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts x Car safety mini drum cable is wrong type material, replace. 1/28/2025
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)7 x Door force exceeds 30#. Adjust as needed.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency light not working. 2/12/2020
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current State Elevator Certificate.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current State Elevator Certificate.
MO Minimum : Elevators (H) - Machine Rooms (H)2 x Provide machine room door to be self closing.
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) x Provide pit light to work.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x The elevator ADA telephone inside the elevator is not addressing its location properly. Check and repair the programming to give the proper location of this phone for passenger safety. Reinspection required. 2/8/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x The elevator ADA telephone inside the elevator is not addressing its location properly. Check and repair the programming to give the proper location of this phone for passenger safety. Reinspection required. 1/25/2024
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)7 The elevator car door closing force is over the maximum allowable force of 30lbs. Readjust door closing force to be less than 30lbs.
MO Minimum : Elevators (H) - Machine Rooms (H)2 The elevator machine room door shall be self-closing/self-locking and shall be operable from the interior space without the use of a key.
MO Minimum : Elevators (H) - Machine Rooms (H)2 The elevator machine room door shall be self-closing/self-locking and shall be operable from the interior space without the use of a key.
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) The elevator pit light did not work on the day of inspection, repair for proper illumination of the pit floor.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts x The elevator safety drum rope was replaced at some point in time with a non-code conforming material. Safety drum rope must be of a corrosion-resistant non ferrous material and not be of tiller rope construction. Reinspection and safety test is required. 1/25/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts The elevator safety drum rope was replaced at some point in time with a non-code conforming material. Safety drum rope must be of a corrosion-resistant non ferrous material and not be of tiller rope construction. Reinspection and safety test is required.
MO Minimum : Elevators (F) - Electrical Switches (F)1 x The stop switch in the elevator has degraded and does not operate properly. Repair or replace switch. 2/8/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts Worm shaft seal is worn and leaking. Repair or replace as needed.