Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1001.2(d)(12) - A completed fire service testing log shall be kept on-site. 11/26/2019
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1001.2(d)(12) - Phase 2 fire service operating instructions in the car are worn and unreadable and shall be replaced. 11/26/2019
A17.1-1996 : Elevators 1.16 - Rated load, platform area, and data plate 1001.2(a)(16) The capacity plate in the car is worn and unreadable and shall be replaced. 11/26/2019
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Display the current state operating certificate. 11/26/2019
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures are missing. (This item is for notification purposes for future violation in 2022) 11/27/2021
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO state operating certificate shall be displayed in the elevator machine room. 11/27/2021
A17.1-1996 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test. 11/27/2021
A17.1-1996 : Elevators 1.16 - Rated load, platform area, and data plate 207 A capacity plate listing the capacity in pounds and prominently displayed in the car enclosure. 11/12/2024
A17.1-1996 : Elevators 2.3 - Lighting and receptacles 101.5a Lighting The machine room light fixture shall be properly fastened to the ceiling in a permanent fashion. 11/12/2024
MO Minimum : Elevators (I) - Pits (I)1 The pit has an excessive amount of water in it. Take corrective action as needed. 11/22/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x The auxiliary power lowering operation shall be functional.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates The fire service phase one key-switch bezel shall be legible. 11/12/2024