Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1001.2(b)(7) Fire extinguisher needs to be serviced. 9/1/2020
A17.1-1996 : Elevators 2.6 - Ventilation 101.5b AC unit not keeping the room at elevator manufacturers recommended temperature 11/5/2025
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current state operating certificate shall be displayed in the machine room 11/5/2025
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) Need to repair or replace non working light fixture in machine room in front of controller to provide at least 10 fc illumination at floor level 11/5/2025
A17.1-1996 : Elevators 2.6 - Ventilation 101.5b HVAC unit is not keeping the machine room at the manufacturer's temperature. 11/5/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency phone in car is not answered. Re-inspection required 11/5/2025
MO Minimum : Elevators (S) - Fire Service 211.3a(8) Visual and audible signal x No audible signal in car when recalled on Phase I fire service, needs repaired. Re-inspection required 11/5/2025