Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x The emergency car lighting is not operational.The fixture shall be repaired to operate. Reinspection required. 9/8/2023
MO Minimum : Elevators (I) - Pits (I)1 The elevator pit floor is covered with debris. The elevator pit shall be kept clean.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Testing incomplete. Unit failed to pick loaded car off safeties (after set safeties at 100% speed/100% load with rope gripper). Need to test: phone, emergency light, emergency alarm, set safeties at 100% speed with 100% load without rope gripper, slide measurement, ACUM. 10/16/2023
A17.1-2016 : Elevators 2.43 - Emergency Brake, Ascending Car Overspeed, and Unintended Car Movement Protection 2.19.2 x Rope gripper OEM data plate states 10,000 lb full load capacity. Car is rated at 12,000 lbs. Install Rope gripper for sufficient capacity. 10/16/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current State Elevator Certificate.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current State Elevator Certificate.
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)6 Front gate safety edge boot is not working. 4/29/2020
A17.1-2016 : Elevators 3.27 - Crosshead Data Plate and Rope Data Tags 2.13.4.2.4 x Crosshead data plate missing. 10/16/2023
A17.1-2016 : Elevators 3.8 - Top emergency exit 2.14.1.5 x Cartop exit panel mesh is broken. Repair 10/16/2023