Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 3.23 - Suspension Means 8.6.4.1 No No Minimum bottom clearance for counterweights shall measure no less than 6.5 inches. Measurements for this inspection proved 5 inches. Ropes shall be shortened.
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No The emegency phone shall establish 2-way communication.
conversion conversion conversion - reinspect Yes No Emergency phone not working 6/6/2018
conversion conversion conversion - reinspect Yes No Emergency phone not working 8/17/2018
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) Yes No Car is running with the car door open. 2/22/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) Yes No The emergency car lighting is not operational, likely indicating that the back-up power device (battery) has failed. The fixture shall be repaired to operate. Reinspection required. 2/7/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) Yes No When testing the audible signaling device (alarm bell) with the 110V disconnect in the machine room in the “off” position, the device failed to sound, indicating that the back-up power device (battery) has failed. Repair for proper operation. Reinspection required. 2/7/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No When testing the ADA telephone with the 110V disconnect in the machine room in the “off” position, the device failed to operate, indicating that the back-up power device (battery) has failed. Repair for proper operation. Reinspection required. 2/7/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post current State Elevator Certificate. 5/9/2025
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post current State Elevator Certificate. 5/9/2025
MO Minimum : Elevators (I) - Pits (I)7 No No The enclosed stop switch in the pit shall meet A17.1 1995 which requires the switch to be marked red. 5/13/2025
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) No No The elevator pit light did not work on the day of inspection, repair for proper illumination of the pit floor. 5/13/2025
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) No No The elevator pit light did not work on the day of inspection, repair for proper illumination of the pit floor. 5/13/2025
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No The elevator machine room door shall be self-closing/self-locking and shall be operable from the interior space without the use of a key. Repair the self-closing device. 5/13/2025
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Yes No Provide pit light to work. 11/19/2025