Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 4.12 - Standby power selection switch 2.27.2 Provide testing of the elevator emergency power selector switch (located in the fire control room).
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current state operating certificate shall be displayed in the machine room
conversion conversion n/a The elevator pit area cannot be used for storage. Remove the items being stored in the pit area to avoid combustibles being stored in a fire rated enclosure. 8/22/2018
A17.1-2016 : Elevators 2.13 - Governor, Overspeed Switch, and Seal 8.6.4.20.2 x x Governor rope pull thru force is over 1000 lbs. Repair / replace governor ro get correct pull thru force. Red-tagged and removed from service. Re-inspection required 2/14/2023
A17.1-2016 : Elevators 2.13 - Governor, Overspeed Switch, and Seal 8.6.4.20.2 x Check car governor switch and jaw tripping speeds. Re-inspection required 2/14/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Test car safeties at rated speed and rated load. Re-inspection required 2/14/2023
A17.1-2016 : Elevators 1.17 - Standby power operation 2.27.2 x Provide testing of the elevator on emergency power. 1/14/2025