MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Test car safeties at rated speed and rated load. Re-inspection required
|
2/14/2023
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
2.27.2
|
x
|
|
Provide testing of the elevator on emergency power.
|
1/14/2025
|
A17.1-2016 : Elevators
|
4.12 - Standby power selection switch
|
2.27.2
|
|
|
Provide testing of the elevator emergency power selector switch (located in the fire control room).
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A copy of the current state operating certificate shall be displayed in the machine room
|
|
A17.1-2016 : Elevators
|
2.13 - Governor, Overspeed Switch, and Seal
|
8.6.4.20.2
|
x
|
x
|
Governor rope pull thru force is over 1000 lbs. Repair / replace governor ro get correct pull thru force. Red-tagged and removed from service. Re-inspection required
|
2/14/2023
|
A17.1-2016 : Elevators
|
2.13 - Governor, Overspeed Switch, and Seal
|
8.6.4.20.2
|
x
|
|
Check car governor switch and jaw tripping speeds. Re-inspection required
|
2/14/2023
|
conversion
|
conversion
|
n/a
|
|
|
The elevator pit area cannot be used for storage. Remove the items being stored in the pit area to avoid combustibles being stored in a fire rated enclosure.
|
8/22/2018
|