MO Minimum : Elevators (F) - Electrical Switches (F)2 x The final limit switch in the pit shall be adjusted to activate before the buffer switch is activated. Currently the counterweight measurement is 3.5” and is activating before the normal directional and final limit switch activates. 1/24/2024
MO Minimum : Elevators (H) - Machine Rooms (H)2 The elevator machine room door shall be self-closing/self-locking and shall be operable from the interior space without the use of a key. Repair the self-closing device.
MO Minimum : Elevators (I) - Pits (I)7 The enclosed stop switch in the pit shall meet A17.1 1995 which requires the switch to be marked red.
A17.1-2016 : Elevators 1.20 - Earthquake Inspection and Tests (Seismic Risk Zone 2 or Greater) 8.11.2.1.1(y) The seismic detection operation of the elevator did not operate as designed. The elevator failed to open the car door automatically as required when the counterweight detection device was activated. Repair the programming of this feature to operate as required.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current State Elevator Certificate.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current State Elevator Certificate.