Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency alarm shall work 7/22/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records Coated steel belt monitor communication was disabled. Communication was re-established, but no maintenance records found of this or any other event in elevator machine room. provide unit maintenance records
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency alarm shall work.
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x Fire Service Phase 1 & 2 must be tested, Re-inspection required 5/31/2023
A17.1-1996 : Elevators 1.6 - Car emergency signal 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Alarm button on Main COP not working. 11/18/2019
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Perform the following tests to complete 5 year inspection: car safeties, car buffer, counterweight buffer, 125% brake, unintended movement 7/22/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Perform the following tests to complete 5 year inspection: car safeties, car buffer, counterweight buffer, 125% brake, unintended movement
A17.1-2016 : Elevators 2.13 - Governor, Overspeed Switch, and Seal 2.18.1 x x Overspeed governor exceeded maximum allowable pull through measurement. Red tagged. Replace governor and governor rope and retest 7/22/2024
A17.1-1996 : Elevators 2.29 - Car and counterweight safeties 1002.2b x x Safety rod bent on top of the elevator. Did NOT red tag. Reinspect only. 11/18/2019
A17.1-1996 : Elevators 2.29 - Car and counterweight safeties 1002.2b x x Repair bent safety actuating link rod on car crosshead. 1/22/2021
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 Coated steel belt monitor communication disabled. Communication re-established but no maintenance records found of this, or any other event, in elevator equipment room. Provide unit maintenance records.
A17.1-2016 : Elevators 3.23 - Suspension Means 8.11.2.1.3(cc) x Belt monitor showing bad belts, Unit turned off. Re-inspection required 5/31/2023
A17.1-1996 : Elevators 3.23 - Suspension rope 1200.4d x Suspension belts showing rouge. Monitor shows replacement. Replace belts in 60 days. 11/18/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.23 - Suspension rope 8.11.2.1.3(cc) x x The hoist belt monitoring system is disabled with visible rouge present on the hoist belts. The hoist belts shall be replaced with the hoist belt monitoring being re-enabled with an alteration permit being issued and a reinspection performed before the elevator shall be returned to service.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.4 Access to Pit door to access pit equipment shall be lockable to prevent access by non elevator personnel
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.4 door to access pit equipment shall be lockable to prevent access by non elevator personnel
conversion conversion conversion - reinspect x Repair bent safety actuating link rod on car crosshead. (Governor sheave gauge bottoms on "C" measurement). 1/15/2019