Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 1.6 - Car emergency signal 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Alarm button on Main COP not working. 11/18/2019
A17.1-1996 : Elevators 2.29 - Car and counterweight safeties 1002.2b Yes Yes Safety rod bent on top of the elevator. Did NOT red tag. Reinspect only. 11/18/2019
A17.1-1996 : Elevators 3.23 - Suspension rope 1200.4d Yes No Suspension belts showing rouge. Monitor shows replacement. Replace belts in 60 days. 11/18/2019
A17.1-1996 : Elevators 2.29 - Car and counterweight safeties 1002.2b Yes Yes Repair bent safety actuating link rod on car crosshead. 1/22/2021
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No Coated steel belt monitor communication disabled. Communication re-established but no maintenance records found of this, or any other event, in elevator equipment room. Provide unit maintenance records. 12/8/2025
A17.1-2016 : Elevators 3.23 - Suspension Means 8.11.2.1.3(cc) Yes No Belt monitor showing bad belts, Unit turned off. Re-inspection required 5/31/2023
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.4 No No door to access pit equipment shall be lockable to prevent access by non elevator personnel 12/8/2025
A17.1-2016 : Elevators 2.13 - Governor, Overspeed Switch, and Seal 2.18.1 Yes Yes Overspeed governor exceeded maximum allowable pull through measurement. Red tagged. Replace governor and governor rope and retest 7/22/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.4 Access to Pit No No door to access pit equipment shall be lockable to prevent access by non elevator personnel 12/8/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.23 - Suspension rope 8.11.2.1.3(cc) Yes Yes The hoist belt monitoring system is disabled with visible rouge present on the hoist belts. The hoist belts shall be replaced with the hoist belt monitoring being re-enabled with an alteration permit being issued and a reinspection performed before the elevator shall be returned to service. 6/5/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.5 Illumination of Pits No No Pit light not working
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Phone not working
conversion conversion conversion - reinspect Yes No Repair bent safety actuating link rod on car crosshead. (Governor sheave gauge bottoms on "C" measurement). 1/15/2019
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Perform the following tests to complete 5 year inspection: car safeties, car buffer, counterweight buffer, 125% brake, unintended movement 6/5/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No Emergency alarm shall work. 6/5/2025
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Means of two-way communication are inoperable and shall be repaired, or replaced. 12/8/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates No No Fire service Phase I operation instructions in main lobby are rubbed off, need to replace signage. 12/8/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts No No T Cable showing signs of wear. Repair or replace. 12/8/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No No Coated steel belt monitor communication was disabled. Communication was re-established, but no maintenance records found of this or any other event in elevator machine room. provide unit maintenance records 12/8/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Perform the following tests to complete 5 year inspection: car safeties, car buffer, counterweight buffer, 125% brake, unintended movement 7/22/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No Emergency alarm shall work 7/22/2024
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) Yes No Fire Service Phase 1 & 2 must be tested, Re-inspection required 5/31/2023