Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts Fire service phase I instructions at lobby are rubbed off. Replace
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Perform the following tests to complete 5 year inspection: car safeties, car buffer, counterweight buffer, 125% brake, unintended movement.
A17.1-1996 : Elevators 2.13 - Governor,overspeed switch and seal 1001.2(b)(28) x x Repair or replace bent safety link rod on car crosshead. Governor sheave gauge bottoms on "C" measurement. Broken parts noticed below governor sheave, replace car governor as well. 3/13/2020
A17.1-1996 : Elevators 2.29 - Car and counterweight safeties 1002.2b x x Safety rod bent on top of elevator. Did NOT red tag. Reinspect only. 11/19/2019
conversion conversion conversion - reinspect x Repair bent safety actuating link rod on car crosshead. (Governor sheave gauge bottoms on "C" measurement). 1/15/2019