Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion conversion - reinspect Yes No Repair bent safety actuating link rod on car crosshead. (Governor sheave gauge bottoms on "C" measurement). 1/15/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts No No Fire service phase I instructions at lobby are rubbed off. Replace 12/8/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.5 Illumination of Pits No No Pit Light not working
A17.1-1996 : Elevators 2.29 - Car and counterweight safeties 1002.2b Yes Yes Safety rod bent on top of elevator. Did NOT red tag. Reinspect only. 11/19/2019
A17.1-1996 : Elevators 2.13 - Governor,overspeed switch and seal 1001.2(b)(28) Yes Yes Repair or replace bent safety link rod on car crosshead. Governor sheave gauge bottoms on "C" measurement. Broken parts noticed below governor sheave, replace car governor as well. 3/13/2020
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Perform the following tests to complete 5 year inspection: car safeties, car buffer, counterweight buffer, 125% brake, unintended movement. 12/8/2025