Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.5 - Housekeeping 8.6.4.9 Cleaning of Car Tops Clean the car top.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits Clean the pit.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2 x Provide Cat 1 testing of the elevator on emergency power.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.12 - Standby power selection switch 2.27.2 x Provide testing of the elevator emergency power selector switch.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Provide existing phone to work.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.5 Illumination of Pits x Provide pit light to work.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits x Clean the pit.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.5 - Housekeeping 8.6.4.9 Cleaning of Car Tops x Clean the car top.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current State Elevator Certificate.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency light and alarm bell inoperative on normal and battery back-up modes. 12/29/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.5 Illumination of Pits Pit light does not work.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2 x Provide testing of the elevator on emergency power. 1/27/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.12 - Standby power selection switch 2.27.2 Provide testing of the elevator emergency power selector switch (located in the fire control room).
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.3 - Lighting and receptacles 2.7.5.1 Lighting Numerous bulbs out in the machine room, repair/replace as needed.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current State Elevator Certificate.