MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.3.1 Replacement Parts
|
|
|
Counterweight rollers excessively noisy, replace.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.4.9 Cleaning of Top of Cars
|
|
|
Clean the car top.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.3.1 Replacement Parts
|
|
|
Provide missing bottom door guide-8th floor (hoistway door).
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.17 - Standby power operation
|
2.27.2
|
x
|
|
Provide testing of the elevator on emergency power.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.5 - Car lighting and receptacles
|
2.14.7.4 Protection of Light Bulbs and Tubes
|
|
|
Elevator cab lights must be protected in case of breakage. Put new cover on or put protective breakage tubes over bulbs
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Provide existing phone to work properly.
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Provide test: unintended movement, record results.
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Provide test: ascending car, record results.
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Provide Cat 5 car safety test, record slide.
|
|
A17.1-1996 : Elevators
|
2.13 - Governor,overspeed switch and seal
|
1002.3b
|
x
|
x
|
Sheave groove worn to gauge "C" position condition. Replace governor sheave within sixty (60) days. Did not red tag.
|
2/3/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.19 - Gears, bearings, and flexible couplings
|
8.11.2.1.2(q)
|
|
|
Repair excessive noice in drive sheave, possible bearing failure.
|
2/1/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.3 - Lighting and receptacles
|
8.11.2.1.2(c)
|
|
|
Relamp machine room lighting fixtures.
|
2/1/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
4.12 - Standby power selection switch
|
2.27.2
|
x
|
|
Provide testing of the elevator emergency power selector switch.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.6.4.7 Cleaning of Pits
|
|
|
Clean pit and hoistway.
|
2/1/2021
|