Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Emergency phone is not working. Re-inspection required 1/2/2025
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Emergency phone in car shall work. Re-inspection required
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting The cab ceiling is of the open egg crate type, which does not provide protection from the light bulbs should they shatter. The lights shall be guarded by plastic sleeve of some other means to properly protect passengers
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) x Need to adjust fascia for car door restrictor to work. Re-inspection required
A17.1-1996 : Elevators 4.2 - Hoistway doors 1001.2(d)(2) Reinstall non vision wings on hall doors.
A17.1-1996 : Elevators 2.3 - Lighting and receptacles 101.5a Lighting A light fixture in the machine room was not operational, repair fixture to provide adequate lighting for maintenance and emergency personnel.
A17.1-1996 : Elevators 4.2 - Hoistway doors 110 The door space/site guards are missing on the bottom and top landing hoistway doors. Reinstall guards to meet code requirements.
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7 The cab ceiling is of the open egg-crate type, which does not provide protection from the light bulbs should they shatter. The lights shall be guarded by plastic sleeve or some other means to properly protect passengers.
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Display updated certificate in machine room.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current state operating certificate shall be displayed in the machine room
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current state operating certificate shall be displayed in the machine room
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates The fireman’s emergency service phase II operation signage is missing inside the elevator cab, reinstall signage for emergency personnel.
conversion conversion n/a Re-in