MO Minimum : Elevators
|
(A) - Hoistways
|
(A)14
|
|
|
Install beveled guard at all landing sills. Guards to extend to depth of leveling zone plus 3 inches.
|
9/24/2024
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)3
|
|
|
Top of car emegency exit needs to be locked on the top side of the elevator.
|
9/24/2024
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)3
|
|
|
Emergency exit cover needs to be attached to cartop with chain or hinge, and needs to be lockable from the car top.
|
9/24/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
|
|
In case of fire don't use elevator signage needed
|
9/24/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4.1(a) On-Site Maintenance Records (MCP Records)
|
|
|
MCP has not been initiated.
|
9/24/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
Post emergency evacuation of passengers procedure form inside machine room.
|
9/24/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
Provide maintenance records on site, or viewable on site, of maintenance control plan.
|
9/24/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4.1(a) On-Site Maintenance Records (MCP Records)
|
|
|
MCP needed
|
9/24/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
Provide MCP in machine room to log maintenance, repairs, and inspections.
|
9/24/2024
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)4
|
|
|
Remove all non-elevator related items from machine room. (boxes)
|
9/24/2024
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
Machine room door needs to be self-locking
|
9/24/2024
|
MO Minimum : Elevators
|
(K) - Car Platforms and Car Slings
|
(K)5
|
|
|
Install toe guard (apron) to car platform.
|
9/24/2024
|
MO Minimum : Elevators
|
(S) - Fire Service
|
211.7 Firefighters Operations/Signage
|
|
|
Post firefighters phase 2 operation instructions inside elevator.
|
9/24/2024
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.6.11.1 Monthly Test and Log
|
|
|
Monthly test and log of firefighters operation.
|
9/24/2024
|
A17.1-2016 : Elevators
|
2.34 - Flexible Hydraulic Hose and Fitting Assemblies
|
8.6.5.6
|
|
|
Flexible hose from tank to shut off valve has no data tag, age unknown. Replace hose and provide new data tag.
|
9/24/2024
|
A17.1-2016 : Elevators
|
2.34 - Flexible Hydraulic Hose and Fitting Assemblies
|
8.6.5.6
|
x
|
|
Flex hose in the Hydrualic Oil line located in the Elevator Machine room has never been tagged as to the installation occurred. Flex House must be replaced every six years. Or the area the hose incompasses hard piped
|
9/9/2024
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Current State Operating Certificate not available. The violations noted on 9/2023 annual inspection have been corrected.
|
9/24/2024
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Current State Operating Certificate unavailable.
|
9/24/2024
|