Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection Unit has oil recovery pump in pit which is for temporary use only. Replace with proper container to allow measurement of oil leakage.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing OSV is not sealed. Perform OSV test on or before next annual inspection date.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.4 Plunger Gripper Testing Plunger gripper is not sealed. Perform test on or before next annual inspection date.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current State Elevator Certificate.
MO Minimum : Elevators (I) - Pits (I)1 Sump hole has oil, remove.
MO Minimum : Elevators (I) - Pits (I)1 Determine if the sump pump works, if not replace.
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x Provide testing of the elevator on emergency power. 12/7/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x Car not working, repair as needed. Reinspect. 1/23/2023