MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(1) Minimum Standard
|
x
|
|
Car not working, repair as needed. Reinspect.
|
1/23/2023
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Sump hole has oil, remove.
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Determine if the sump pump works, if not replace.
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current State Elevator Certificate.
|
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
x
|
|
Provide testing of the elevator on emergency power.
|
12/7/2024
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.4 Plunger Gripper Testing
|
|
|
Plunger gripper is not sealed. Perform test on or before next annual inspection date.
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing
|
|
|
OSV is not sealed. Perform OSV test on or before next annual inspection date.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.5.5.2 Oil Leakage Collection
|
|
|
Unit has oil recovery pump in pit which is for temporary use only. Replace with proper container to allow measurement of oil leakage.
|
|