Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x Car not working, repair as needed. Reinspect. 1/23/2023
MO Minimum : Elevators (I) - Pits (I)1 Determine if the sump pump works, if not replace.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing OSV is not sealed. Perform OSV test on or before next annual inspection date.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.4 Plunger Gripper Testing Plunger gripper is not sealed. Perform test on or before next annual inspection date.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current State Elevator Certificate.
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x Provide testing of the elevator on emergency power. 12/7/2024
MO Minimum : Elevators (I) - Pits (I)1 Sump hole has oil, remove.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection Unit has oil recovery pump in pit which is for temporary use only. Replace with proper container to allow measurement of oil leakage.