Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (N) - Guide Rails (N)1 Loose guide rail bracket in hoistway
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)4 Idler sheave on door operator is loose
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers Fire Extinguisher in Machine Room is due to be serviced or replaced
MO Minimum : Elevators (I) - Pits (I)1 Remove oil from pit floor
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing Unsealed overspeed valve due to be tested with rated load. Recurring every 5 years
MO Minimum : Elevators (I) - Pits (I)1 All pits shall be kept dry, clean, and free of equipment or material not relating to the operation of the elevator. Oil on the pit floor
MO Minimum : Elevators (H) - Machine Rooms (H)4 Articles or materials not necessary for the maintenance or operation of the elevator shall not be stored in machine room
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates Provide signage at each landing instructing occupants that, "In case of Fire, Elevator is out of service"
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) x When a car is outside the unlocking zone, the car doors shall be so arranged that when in the closed position they shall be restricted from opening
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency Phone in car fails to establish two-way communication
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) x Overspeed valves, where provided, shall be inspected and tested to verify that they will stop the car, traveling down with rated load every 5 years.
MO Minimum : Elevators (S) - Fire Service (S)1 x Need Phase II fire service instructions 5/2/2022
MO Minimum : Elevators (S) - Fire Service (S)1 x Stop switch in car is not overridden during Phase I recall 5/2/2022