Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection Unit has oil recovery pump in pit which is for temporary use only. Replace with proper container to allow measurement of oil leakage.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing OSV is not sealed. Perform test on or before next annual inspection date.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.4 Plunger Gripper Testing Plunger gripper is not sealed. Perform test on or before next annual inspection date.
MO Minimum : Elevators (I) - Pits (I)1 Sump unit not plugged in. Determine if working, if not-replace.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current State Elevator Certificate.
MO Minimum : Elevators (I) - Pits (I)1 Sump hole has oil in it, remove.
MO Minimum : Elevators (I) - Pits (I)1 Determine if the sump pump works properly, if not then replace.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current State Elevator Certificate.
A17.1-2016 : Elevators 4.12 - Standby power selection switch 2.27.2 x Provide testing of the elevator emergency power selector switch.
A17.1-2016 : Elevators 1.17 - Standby power operation 2.27.2 x Provide testing of the elevator on emergency power.
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.11.1.3 Emergency Phone not workng Alarm Functioning ( Mandatory Re-Inspection due in 14 days) x Phone works,but goes to the previous contractor., reprogram.
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x Provide testing of the elevator on emergency power. 12/7/2024
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x Phase II switch improperly mounted in COP, unable to test. Repair as needed. 5/10/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Provide testing of emergency power. 5/10/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Provide testing of emergency power selector switch. 5/10/2023