MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone shall be made operational. Re-inspection required
|
6/17/2024
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone is not working. Re-inspection required
|
3/31/2025
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Provide existing emergency lights and bell to work properly.
|
|
MO Minimum : Elevators
|
(F) - Electrical Switches
|
(F)1
|
x
|
|
There shall be a switch in the elevator disconnect that will not allow the emergency lowering device to operate when the disconnect is turned off. Re-inspection required
|
3/31/2025
|
MO Minimum : Elevators
|
(F) - Electrical Switches
|
(F)9
|
|
|
There shall be a switch in the elevator disconnect that will not allow the emergency lowering device to operate when the disconnect is turned off
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.5.5.2 Oil Leakage Collection
|
x
|
|
Remove old scavenger line.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.5.5.2 Oil Leakage Collection
|
x
|
|
Remove scavenger unit from the pit.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.5.5.2 Oil Leakage Collection
|
|
|
Provide pit bucket.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.5.5.2 Oil Leakage Collection
|
|
|
Remove scavenger line from tank.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.5.5.2 Oil Leakage Collection
|
|
|
Remove scavenger pump from pit.
|
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
3.26.10
|
x
|
|
Emergency lowering device shall be made operational. Re-inspection required
|
6/17/2024
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
x
|
|
Emergency lowering device is not operational. Re-inspection required
|
3/31/2025
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing (Re-Inspect)
|
x
|
|
OSV is not sealed or tagged and testing shall be performed within 30 days. Re-inspection required
|
6/17/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing
|
|
|
OSV is not sealed. Perform test on or before next annual inspection.
|
6/4/2021
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Battery backup lowering unit not working correctly, repair/ replace as needed.
|
5/2/2023
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.4.1(a)(1)
|
|
|
Provide MCP
|
|
A17.1-2016 : Elevators
|
5.15.2 Unsealed Overspeed Valve
|
8.6.5.16.5 (Re-Inspect)
|
x
|
|
OSV unsealed.
|
5/2/2023
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current State Elevator Certificate.
|
|