A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone shall work.
|
7/8/2020
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
1001.2(d)12
|
x
|
|
Fireman's light at Lobby shall work.
|
7/8/2020
|
A17.1-2016 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
|
|
Provide current year tested fire extinguisher in the elevator mechanical space.
|
9/25/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.2 - Stop switches
|
2.26.2.21
|
|
|
Stop switch is loose(COP), repair as needed.
|
9/25/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone in car shall work, appears to have no live phone line. Re-inspection required
|
11/9/2022
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)6 (Pit Lighting)
|
|
|
Provide top of hoistway light to work properly.
|
9/25/2024
|
MO Minimum : Elevators
|
(S) - Fire Service
|
211.8 Switch Keys
|
|
|
Phase I lobby plate ( holding switch) is damaged, replace as needed.
|
9/25/2024
|